Technical information

Rated voltage 12 kV 17.5 kV 24 kV
Rated frequency 50/60 Hz 50/60 Hz 50/60 Hz
Rated insulation level (AC)28 kV 38 kV50 kV
Rated insulation level (impulse voltage) 75 kV 95 kV 125 kV
Rated current 630-4000 A 630-4000 A 630-1600 A
Rated short-circuit currents ----------- ----------- -----------
- Short time withstand current 40 kA 40 kA 25 kA
- Peak withstand current100 kA  100 kA 63 kA
Internal arc fault withstand ----------- ----------- -----------
- Main busbar 40 kA, 1s 40 kA, 1s 40 kA, 1s
- CB-compartment 31.5 kA, 1s 31.5 kA, 1s 31.5 kA, 1s
- Cable-compartment 25 kA, 1s 25 kA, 1s 25 kA, 1s

We use only leading technology components from globally recognised manufacturers. We work with our customers to choose the most cost-efficient components for their specifc end uses.

VEKE 24 is certified for compliance with the high-performance requirements of the latest IEC standards.